45 Appendix D
D.1 Voltage Calibration Procedure
1. Click the Setup button on the Advantech Device Manager window
(Fig.1) to launch the PCI-1724U Device Setting window (Fig.2).
Figure D.1: Click the Setup button to Launch the Device Setting
2. Select the output range of the channel to –10V~10V.
3. Click the Calibration button to start the calibration process. The
Calibration Wizard window will pop up.
Note Each calibration process can calibrate only one chan-
nel and one input range at a time.