Command Set 5017H/5017UH
Analog Input
$aaSiAFFff
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh).
Example command: $35S3AFF00(cr)
response: !35(cr)
The data format of the ADAM-5017H / 5017UH module in
slot 3 of the ADAM-5000 system at address 35h is
configured for engineering unit format. The response
indicates that the command has been received as a valid
command.