Digital I/O and Relay Output
Counter/Frequency Command Set
7-
70
ADAM 4000 Series User’s Manual
@AADI
Example command: @15DI(cr)
response: !1510000(cr)
The counter module at address 15h is instructed to return
digital output data and alarm status. The module responds
that both digital output channels are OFF and alarm state is
MOMENTARY.
command: @05DI(cr)
response: !0530000(cr)
The counter module at address 05H is instructed to return
digital output and alarm status. The module responds that
both digital output channels are OFF and the alarm status
for both counters are ENABLED.