Advantech Data Acquisition Modules ADAM 4000 Manuale Utente Pagina 328

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 429
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 327
Calibration
8-
16
ADAM 4000 Series User’s Manual
4. Execute the Span Calibration command. This can be done through
the ADAM utility software. (Please see "A/O 10 V Calibration"
option in the Calibration sub-menu of the ADAM utility software.)
Figure 8-9 Span Calibration
5. Check the actual output value at the terminals. If this does not equal
0 V or 10 V, use the Trim Calibration command to change the
output value. This is done through the ADAM utility software.
(Use the arrow key to adjust the output value after executing the
"A/O 0V Calibration" or "A/O 10 V Calibration". Right and Up
keys mean increasing, and Left and Down keys mean decreasing).
Vedere la pagina 327
1 2 ... 323 324 325 326 327 328 329 330 331 332 333 ... 428 429

Commenti su questo manuale

Nessun commento